A polymer preparation unit makes a usable solution and a dosing pump meters it into sludge. A belt filter press then dewaters the conditioned sludge. Identify both equipment packages and the connections between them when comparing quotes.
Where do preparation, dosing and dewatering happen?
The preparation unit makes or dilutes polymer solution. The pump delivers it to the injection point. The belt press drains and compresses the conditioned sludge and sends cake and filtrate to separate outlets.
Which equipment is needed for dry polymer?
Ask suppliers to identify powder feed, the wetting step, maturation volume and solution storage. Confirm the required preparation water and what happens if the feeder runs out.
Which equipment is needed for liquid polymer?
Identify the supplied polymer concentration and product type. Confirm dilution, product compatibility and any required activation step with the chemical and equipment suppliers.
What makes a pump or preparation unit suitable for the press?
Compare solution delivery at the low, normal and maximum dry-solids loads. Check that the unit can prepare and deliver solution through a full shift and recover after a pause.
What should a purchase quote list?
Ask for the included preparation, storage and metering equipment. Confirm utilities, priming and cleaning connections, instruments, spare parts and the scope of commissioning.
What should an acceptance test measure?
Measure delivered solution concentration or preparation records and actual dosing flow. At the press, record cake dry solids, filtrate solids, accepted feed and active polymer dose per dry tonne.
What controls help operators respond to faults?
Document the response to low polymer, loss of preparation water or delivery flow, and departure from the accepted sludge load range. Test the alarms during commissioning.
What should be shared between equipment vendors?
Share a process sketch from storage through injection and the press. Assign responsibility for piping, instruments, interlocks and verifying both the solution and treated outlet.
Inputs for equipment selection
Provide the polymer product, sludge variability, dry-solids throughput, solution flow range, pressure at injection and available water and electrical service.
Review the belt filter press and bring the measurements above to PORVOO for equipment selection.